Intel study shows data centres need not be cool

by Iain Thomson

More from this author

19 Sep 2008

Comment: 1

  • Tweet this
Data centre
Intel has achieved surprising results using an 'air economiser' in a test data centre

A pilot study on data centre cooling has shown that systems architects may be over-specifying data centre operations.

Intel set up a trial data centre (PDF) of 900 blade servers split into two sections. One side was run in the traditional manner, with air-conditioners and dust filters, and the other used an air economiser which simply sucked out hot air and replaced it with outside air at normal temperature without adjusting for temperature or humidity.

The results were surprising. The unfiltered, un-cooled data centre machines suffered a failure rate of 4.46 per cent, compared to 3.83 per cent for the air conditioned centre, despite having an internal air temperature of around 90 degrees Fahrenheit.

Air in the un-cooled centre was passed through simple household dust filters. The servers became covered with a thick layer of dust over the 10-month trial period but this did not seem to affect reliability.

If the results are extrapolated to a 10-megawatt data centre, Intel estimates that it could cut power consumption by 67 per cent, yielding a cost saving of $2.87m per annum.

"A data centre equipped with an air economiser could substantially reduce Intel's environmental footprint by reducing consumption of power and water," said Don Atwood, regional data centre manager at Intel Information Technology.

"In dry climates, traditional air-conditioned data centres typically include evaporative cooling using water towers as a pre-cooling stage.

"With an economiser, this would not typically be used, potentially saving up to 76 million gallons of water annually in a 10-megawatt data centre."

The test centre was set up in a dry, temperate desert and the results suggest that data centres are capable of operating perfectly well at temperatures approaching 90 degrees Fahrenheit and using much less expensive air conditioning equipment.

The company is now planning on building a 1-megawatt test facility and conducting a longer trial to get a more accurate picture of reliability rates.

Do you agree?

 

Add your comment

We won't publish your address
By submitting a comment you agree to abide by our Terms & Conditions. Your comment will be moderated before publication.

Poll

IT priorities for 2012

What is the most important IT priority for your company this year?

99%

0%

1%

0%

0%

Connect with V3.co.uk

Sign up to our daily or weekly newsletters

Accurev

Top 5 software development challenges

This paper focuses on a series of best practices and techniques for development teams looking to improve their software development processes

Talend

Rubbish in, rubbish enterprise

Why good data management at all levels is essential in the modern business (video, 6mins)

Oracle Appplications Support - HR and Payroll

Position:Oracle Applications eBusiness Suite Suport...

Developer

Software Developer A leading UK Software Application...

Senior Drupal Developer - PERM - £55K - URGENT

I am looking for a permanent senior Drupal Developer...

Retail Consultant - Data Transformation and Migration

Retail Consultant - Data Transformation and Migration...

To send to more than one email address, simply separate each address with a comma.